Products

Phoenix Hybrid motor starter - ELR H5-IES-SC- 24DC/500AC-0,6 - 2900582 New & Original with very competitive price and One year Warranty

New & Original
ELR H5-IES-SC- 24DC/500AC-0,6 - 2900582
Phoenix Hybrid motor starter - ELR H5-IES-SC- 24DC/500AC-0,6 - 2900582 New & Original with very competitive price and One year Warranty
Please contact us for more information.

Phoenix Hybrid motor starter - ELR H5-IES-SC- 24DC/500AC-0,6 - 2900582




Hybrid motor starter for reversing 3~ AC motors up to 500 V AC and 0.6 A output current, with 24 V DC control voltage, adjustable overload shutdown, 

emergency stop function to SIL 3/PL e, and screw connection.


Key Commercial Data

Orderkey2900582
Packing unit1 pc
Catalog pagePage 28 (C-5-2019)
GTIN4046356526289
Weight per Piece (excluding packing)300.000 g
Custom tariff number85371098
Country of originDE (Germany)


Dimensions

Width22.5 mm
Height107 mm
Depth114 mm


Ambient conditions

Ambient temperature (operation)-25 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Maximum altitude≤ 2000 m
Degree of protectionIP20


Device supply

Rated control circuit supply voltage US24 V DC
Control supply voltage range19.2 V DC ... 30 V DC
Rated control supply current IS40 mA
Type of protectionSurge protection

Reverse polarity protection


Input data

Input nameControl input right/left
Rated actuating voltage UC24 V DC
Triggering voltage range19.2 V DC ... 30 V DC
Rated actuating current IC5 mA (Input type 1)
Switching threshold9.6 V (“0” signal)

19.2 V (“1” signal)
Switching level< 5 V DC (For EMERGENCY STOP)
Typical turn-off time< 30 ms
Type of protectionReverse polarity protection


Output data load output

Output nameAC output
Rated operating voltage Ue500 V AC
Operating voltage range42 V AC ... 550 V AC
Rated operating current Ie0.6 A (AC-51)

0.6 A (AC-53a)
Mains frequency50/60 Hz
Load current range75 mA ... 600 mA (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2Class 10A
Cooling time20 min. (for auto reset)
Leakage current0 mA
Type of protectionSurge protection


Output data reply output

Output nameAcknowledge output
NoteConfirmation: floating change-over contact, signal contact
Contact type1 PDT
Switching capacity according to IEC 60947-5-13 A (230 V, AC15)

2 A (24 V, DC13)


General

Motor starter typeReversing starter
Switching frequency≤ 2 Hz (Load-dependent)
Mounting positionvertical (horizontal DIN rail, motor output below)
Mounting typeDIN rail mounting
Assembly instructionsalignable, for spacing see derating
Operating mode100% operating factor
Maximum power dissipation1.5 W
Minimum power dissipation1.1 W
Operating voltage displayGreen LED
Status displayYellow LED
IndicationRed LED


Connection data

Connection nameControl circuits
Connection methodScrew connection
Stripping length8 mm
Screw threadM3
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Torque0.5 Nm ... 0.6 Nm

5 lbf-in. ... 7 lbf-in.


Connection data 2

Connection nameLoad circuit
Connection methodScrew connection
Stripping length8 mm
Screw threadM3
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Torque0.5 Nm ... 0.6 Nm

5 lbf-in. ... 7 lbf-in.


Insulation characteristics

Rated insulation voltage500 V
Rated surge voltage6 kV
Overvoltage categoryIII
Degree of pollution2
DesignationInsulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit
InsulationSafe isolation (IEC 60947-1/EN 50178) at operating voltage ≤ 300 V AC

Basic isolation (IEC 60947-1) at operating voltage 300 ... 500 V AC

Safe isolation (EN 50178) at operating voltage 300 ... 500 V AC
DesignationIsolation characteristics between the control input and control supply voltage to auxiliary circuit
InsulationSafe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC

Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC


Standards and Regulations

DesignationStandards/regulations
Standards/regulationsIEC 60947-1

IEC 60947-4-2

IEC 61508

ISO 13849


Conformance/approvals

DesignationATEX
Identification II (2) G [Ex e] [Ex d] [Ex px]

 II (2) D [Ex t] [Ex p]
CertificatePTB 07 ATEX 3145
DesignationUL approval
CertificateNLDX.E228652
DesignationSafety Integrity Level (SIL, IEC 61508)
Identification≤ 3
Additional textSafe shutdown
DesignationSafety Integrity Level (SIL, IEC 61508)
Identification2
Additional textMotor protection
DesignationPerformance Level (ISO 13849)
Identification≤ e
Additional textSafe shutdown
DesignationCategory (ISO 13849)
Identification≤ 3
Additional textSafe shutdown

UL data

SCCR100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))

5 kA (500 V AC (fuse: 20 A RK5 (standard fault)))
FLA0.6 A (500 V AC)
Group installation20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)

30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
Category codeNLDX



Copyright © 2019 Sunup (Wuhan) Industrial Equipment Co., Ltd. All Right Reserved.


Sunup (Wuhan) Industrial Equipment Co., Ltd is not an authorized reseller, agent or affiliate of any brand or manufacturer. All trademarks, brand names and logos whose products are sold on the website are used for identification purposes only and are registered trademarks of their respective owners, all rights reserved. The use of a trademark, brand name or product on our website does not imply that the company trademark or brand belongs to or endorses our website. All products are 100% original, genuine and legally purchased from authorized sources.